Transformateurs de courant à séquence zéro type LJM-1
Overview The LJM-1, LJM-2, LJM-3, and LJM-3L Bus-Type Zero Sequence Current Transformers are advanced indoor transformers designed for accurate zero-sequence current measurement in power systems (Accurate Earthing Protection). These Zero Sequence Current Transformers feature a robust bus-type structure, making them ideal for applications involving three-phase AC generators and motors requiring zero-sequence protection. With a rated […]
Overview
The LJM-1, LJM-2, LJM-3, and LJM-3L Bus-Type Zero Sequence Current Transformers are advanced indoor transformers designed for accurate zero-sequence current measurement in power systems
(Accurate Earthing Protection). These
Zero Sequence Current Transformers feature a robust bus-type structure, making them ideal for applications involving
three-phase AC generators and motors requiring zero-sequence protection.
With a rated frequency of 50Hz or 60Hz and a rated voltage of 15kV or below (commonly used for 6kV, 10kV, and 15kV systems), the LJM series transformers ensure
reliable fault detection and system monitoring. They are specifically paired with the DD11/60 relay for enhanced zero-sequence protection, ensuring safe and efficient operation
in power distribution networks.
Type Designation Explanation
The following is the type designation for the LJM-1, LJM-2, and LJM-3 Zero Sequence Current Transformers:
- L: Current transformer
- J: Earthing protection
- M: Busbar type
- 1, 2, 3: Rated voltage classification
Note: For special requirements or specific customizations, please contact our technical team for tailored solutions.
Operating Conditions for LJM
- Altitude: Not exceeding 1000 meters.
- Ambient Temperature: Between -5°C and +40°C.
- Relative Humidity: Not exceeding 85% at 20°C.
- Installation Environment: Free from severe gases, vapors, chemical deposits, pollution, and other explosive or corrosive substances that could affect the transformer’s insulation.
Structure of LJM Bus-Type Zero Sequence Current Transformer
The LJM Zero Sequence Current Transformer features a bus-type structure, equipped with primary busbars to facilitate convenient installation. When the primary zero-sequence current
reaches the preset threshold, the transformer provides an accurate secondary current output to activate the relay, achieving reliable protection for the electrical system.
Technical Data for LJM
Standards: Current transformers are designed in accordance with the Shanghai Standards Q/JB 3380-84.
Type | LJM-1 | LJM-2 | LJM-3 |
---|---|---|---|
Rated primary current (A) | 1750 | 3000 | 4000 |
Rated secondary current (A) | 5 | 5 | 5 |
Frequency (Hz) | 50 | 50 | 50 |
Ith (kA) | 24 | 48 | 72 |
Idyn (kA) | 2.5 Ith | 2.5 Ith | 2.5 Ith |
Max. short-circuit impulse current (kA) | 165 | 165 | 165 |
Unbalancing Voltage (mV) | <60 | <85 | <100 |
Insulation level (kV) | 6/32 | 10/42 | 15/55 |
For special customizations or technical requirements, please contact our support team.
Outline and Dimensions of Installation
When ordering, please specify the following:
- Insulation level
- Current ratio
- Accurate level and rated secondary load
- Use environment
- For special requirements, please contact our technical team.
FAQs for LJM Bus-Type Zero Sequence Current Transformers
- What are the key applications of the LJM Bus-Type Zero Sequence Current Transformers?
These transformers are designed for zero-sequence current measurement, fault detection, and relay protection in medium-voltage power systems. - What voltage levels are supported by the LJM series?
The LJM series supports voltage levels of 6kV, 10kV, and 15kV, with a maximum rated voltage of 15kV. - Can the LJM transformers be customized for specific needs?
Yes, the transformers can be customized for insulation levels, current ratios, and specific secondary load requirements to suit diverse operational needs. - Which relay is compatible with the LJM transformers for protection purposes?
The LJM transformers are specifically paired with the DD11/60 relay for advanced zero-sequence protection and fault monitoring. - What is the maximum short-circuit current the LJM series can handle?
The LJM transformers can handle maximum short-circuit impulse currents up to 165kA, providing robust protection in fault conditions. - Are the LJM transformers suitable for outdoor installations?
No, the LJM series is designed for indoor use only and requires clean environments free from corrosive gases, pollutants, or significant dust.
- Considérations sur le Traitement des Pannes des Transformateurs de Courant et de Tension
- Points de Mise à Terre Autorisés dans le Circuit Secondaire d’un Transformateur de Tension
- Principe de fonctionnement des transformateurs de courant à séquence zéro
- Effets de la Saturation des Transformateurs de Courant sur la Protection des Transformateurs et du Courant
- Chauffage Anormal dans les Transformateurs de Courant 10KV : Causes, Conséquences et Solutions
- Principe de protection des transformateurs de courant à séquence nulle (ZCT) et applications