GN19-12 Wall-through Type Indoor High Voltage Disconnector

GN19-12 indoor wall-through high voltage AC disconnector for three-phase 50 Hz systems rated 12 kV.

  • Opens and closes no-load circuits under voltage with a visible break; cannot break load or fault current
  • Operated by a CS6-1 manual mechanism with interlock
  • Four rated-current variants: 400 / 630 / 1000 / 1250 A
  • 4 s short-time withstand up to 40 kA and peak withstand up to 100 kA
  • Wall-through pole design with mounting panel for switchgear cubicles
  • Pollution-proof, high-altitude and live-display derived versions available

Overview

The GN19-12 is an indoor, wall-through type high voltage AC disconnector for three-phase 50 Hz systems rated 12 kV. Operated by a CS6-1 manual mechanism, it opens and closes circuits under voltage but without load and cannot break load or short-circuit current. Derived versions include a pollution-proof type, a high-altitude type and a version fitted with a live-display device.

Each pole is built on a common frame with support insulators, outgoing terminals and knife contacts, arranged to pass through the switchgear panel wall (type C, with panel M). Four rated-current variants from 400 to 1250 A are offered, with 4 s short-time withstand up to 40 kA and peak withstand up to 100 kA.

GN19-12 indoor wall-through high voltage disconnector with contact blade, insulator, CS6-1 operating mechanism, base frame and connection terminal detail views

GN19-12 indoor high voltage disconnector poster

Model Designation

GN19-12 indoor high voltage disconnector model designation decoding diagram

The type is designated G N 19 -12 C M / □ – □ and decoded as follows:

  • G — disconnector
  • N — place of use: indoor
  • 19 — design sequence number
  • 12 — rated voltage in kV
  • C — wall-through type
  • M — with mounting panel
  • □ — rated current in A
  • □ — rated thermal-stable (short-time) current in kA

Construction and Operation

  • Wall-through poles. Each pole is carried on a common frame with support insulators and passes through the panel wall so that the disconnector can isolate a section on each side of the cubicle.
  • Current path. Outgoing terminals, support insulators and knife / finger contacts form the main conducting circuit; contact pressure is maintained by self-cleaning fingers.
  • CS6-1 manual mechanism. The poles are operated through a CS6-1 manual operating mechanism with interlock; a live-display device option indicates the energised state.
  • Derived types. Pollution-proof and high-altitude versions are available in addition to the standard indoor type.

Technical Parameters

Rated Parameters

Type designation Rated

voltage

(kV)

Rated

current

(A)

Rated short-time

withstand current

4 s (kA)

Rated peak

withstand (dynamic)

current (kA)

GN19-12CM/400-12.5 12 400 12.5 31.5
GN19-12CM/630-20 12 630 20 50
GN19-12CM/1000-31.5 12 1000 31.5 80
GN19-12CM/1250-40 12 1250 40 100

In the type designation the first figure after the slash is the rated current in A and the second is the rated 4 s short-time (thermal-stable) withstand current in kA; the dynamic-stable (peak) withstand current is listed in the last column.

Normal Service Conditions

  • Altitude: not above 1000 m (a high-altitude version is available)
  • Ambient temperature: −25℃ to +40℃
  • Relative humidity: daily average not above 95%, monthly average not above 90%
  • Seismic intensity: not above intensity 8
  • Site: free from fire hazard, flammable or explosive gases, severe pollution, chemical corrosion and violent vibration

Installation & Wiring

Installation and Mounting

Mount the wall-through poles on their common frame so that the bushings pass through the panel wall, fix the frame through the mounting holes, and couple the poles to the CS6-1 operating mechanism. Verify free travel of the knives, correct contact seating and the full visible break before energising, and bond the frame to the earth network.

GN19-12 indoor high voltage disconnector outline and mounting dimensions drawing

Outline & Mounting Dimensions

  • Frame overall width 620 mm; phase spacing 210 + 210 mm; overall height 470 mm.
  • Panel cut-out: panel length 185 mm, width 150 mm, thickness 50 mm; the 170 mm dimension can be customised.
  • Wall-through bushing projection 182 mm; mechanism side 438 mm; terminal offsets 185 / 240 / 50 mm.
Dimensions are taken from the catalogue outline drawing and are for panel and foundation preparation only; confirm the certified dimensional drawing with the ordered current and mechanism arrangement before installation.

Selection & FAQs

Selection Guide

  • Choose the rated current (400 / 630 / 1000 / 1250 A) to match the feeder; short-time and peak withstand ratings increase with current.
  • Confirm the panel cut-out and wall-through arrangement against the switchgear cubicle.
  • Select the pollution-proof or high-altitude version where the site requires it, and the live-display option where indicated isolation is needed.

Frequently Asked Questions

Q1: What does the type designation GN19-12CM mean?

G is the disconnector, N the indoor place of use and 19 the design sequence number; 12 is the rated voltage in kV, C denotes the wall-through type and M the version with a mounting panel. The trailing figures give the rated current in A and the rated 4 s thermal-stable current in kA.

Q2: Can the GN19-12 break load or short-circuit current?

No. It only opens and closes no-load circuits under voltage and provides a visible isolating gap; load and fault currents are cleared by the associated switching or protective device.

Q3: What mechanism is used?

A CS6-1 manual operating mechanism with interlock; a live-display device can be added to indicate the energised state.

Q4: What rated versions are available?

Four 12 kV variants: 400 A (12.5 kA / 31.5 kA), 630 A (20 kA / 50 kA), 1000 A (31.5 kA / 80 kA) and 1250 A (40 kA / 100 kA), where the values are 4 s short-time and peak withstand currents.

Q5: What are the service conditions?

Altitude up to 1000 m, ambient −25℃ to +40℃, relative humidity daily average up to 95% and monthly average up to 90%, seismic intensity up to 8, and a site free from fire, explosive or corrosive hazards.

Q6: Are derived versions offered?

Yes — pollution-proof and high-altitude types and a version with a live-display device. See the disconnector range for related models.