JDJ2-35, JDJJ2-35 single-phase outdoor oil-immersed potential transformer

2026-03-02

Product Overview

The JDJ2-35 and JDJJ2-35 (also designated as JDXN2-33, JDN2-33) series voltage transformers, are single-phase outdoor oil-immersed potential transformer, this electromagnetic instruments are designed for accurate voltage measurement, energy metering, voltage monitoring, and relay protection applications in 35kV AC power systems operating at 50 Hz or 60 Hz. These transformers utilize electromagnetic induction principles to provide galvanically isolated secondary voltage signals proportional to primary voltage.

Key Ratings

Item Specification (per order / nameplate)
System voltage class 35 kV class (outdoor distribution and substation applications)
Rated frequency 50 Hz (60 Hz available upon request)
Rated primary voltage 33000 V / 33000/√3 V
Rated secondary voltage 100 V / 100/√3 V / 100/3 V
Accuracy classes Metering and/or protection cores as specified (e.g., 0.2, 0.5, 1, 6P)
Rated burden Per core/winding as specified (VA): 30-150 VA for metering, 100 VA for protection
Burden power factor cosφ = 0.8 (lagging) unless otherwise specified by the project standard
Rated insulation level 40.5/95/200 kV (Um/ACWV/LI)
Limiting output 500-1000 VA depending on configuration
Applicable standards GB 1208-1997; IEC 60044-2 (IEC 186)
Structural variants JDJ2-35 (single/dual winding) / JDJJ2-35 (three-winding with residual winding)

Product Shows

JDJ2-35, JDJJ2-35 single-phase outdoor oil-immersed potential transformers Show

Working Principle

Operating on Faraday’s law of electromagnetic induction, the transformer features a three-limb laminated silicon steel core with primary winding on the center limb and secondary windings wound concentrically around the primary. The alternating magnetic flux generated by primary voltage induces proportional voltage in the secondary windings, delivering standardized output voltage through connected burden. Oil immersion provides enhanced insulation and heat dissipation.

System Application Position

Structural Overview

Oil-immersed construction with three-limb laminated silicon steel core ensures superior insulation performance, thermal stability, and mechanical strength. The outdoor post-type mounting configuration provides robust installation in exposed environments while maintaining excellent electrical clearance and creepage distances. JDJJ2-35 incorporates a residual winding for enhanced fault protection capability in systems requiring ground fault detection.

Model Designation

JDJ2 JDJJ2 35 Outdoor Oil Immersed Single Phase Voltage Transformer type

Model Code Explanation

Variant Differences

JDJ2-35 is available in single-winding or dual-winding configurations for basic metering and protection applications. JDJJ2-35 incorporates a three-winding design with residual winding output (100/3 V or 100/√3 V), specifically engineered for applications requiring ground fault detection and enhanced protection coordination in outdoor distribution systems.

Service Conditions

The JDJ2-35 and JDJJ2-35 series voltage transformers are designed for outdoor operation under normal service conditions in medium-voltage power systems.

Engineering Note: The installation location shall comply with applicable electrical safety regulations and provide stable operating conditions throughout the transformer’s service life. Oil level monitoring and periodic maintenance procedures shall be established per applicable standards.

Construction

Construction Design

The oil-immersed structure provides enhanced insulation properties, superior heat dissipation, and effective resistance to moisture and high-temperature environments for long-term outdoor service.

Windings & Terminal Marking

JDJ2 35 JDJJ2 35 single phase outdoor oil immersed potential transformer input output

JDJ2-35 (single/dual winding):

JDJJ2-35 (three-winding):

Terminal markings follow standard VT polarity conventions. Under normal operating conditions, when primary terminal A is positive relative to X, secondary terminal a is positive relative to x. Correct terminal identification shall be observed to ensure metering and protection performance.

Technical Data

This section provides selection-oriented technical data for the JDJ2-35 and JDJJ2-35 series outdoor, oil-immersed voltage transformers used in 35 kV class AC systems (50 Hz). Data shown below is intended for preliminary selection of voltage ratio, accuracy class combinations, and rated burdens.

Definitions: Accuracy class combination indicates available metering/protection cores in one VT (multi-core configuration may apply). Rated output (VA) is specified per secondary core. Limiting output (VA) is the maximum continuous thermal capacity of the transformer under specified operating conditions.

Data Reference

Model Rated
Voltage
Ratio (V)
Rated
Output
(VA)
Rated
Output
(VA)
Rated
Output
(VA)
Rated
Output
(VA)
Limiting
Output
(VA)
0.2 0.5 1 6P
JDJ2-33 33000/100 50 100 150 1000
JDJJ2-33 33000/√3 / 100/√3 / 100/3 50 100 150 100 2 × 500
JDJJ2-33 33000/√3 / 100/√3 / 100/√3 / 100/3 30 60 100 2 × 500

Standards & Normative References

Standard Title Application
GB 1208-1997 Voltage Transformers National VT standard (primary compliance basis)
IEC 60044-2 Instrument Transformers – Part 2: Inductive Voltage Transformers International VT requirements (IEC 186 superseded)
IEC 61869-3 Instrument Transformers – Part 3: Additional Requirements for Inductive Voltage Transformers Updated international VT standard
GB/T 20840.3 Instrument Transformers – Part 3: Inductive Voltage Transformers National standard (aligned with IEC 61869 framework)
DL/T 866 Technical Specification for Oil-Immersed Voltage Transformers Power utility technical requirements
GB 311.1 Insulation Co-ordination – Part 1: Definitions, Principles and Rules Insulation level coordination

Factory Test Compliance

Installation & Dimensions

Outlines

JDJ2 JDJJ2 35 Outdoor Oil Immersed Single Phase Voltage Transformer outline 2

JDJ2-35 Dimensional Drawing

JDJ2 JDJJ2 35 Outdoor Oil Immersed Single Phase Voltage Transformer outline 2 1
JDJJ2-35 (JDXN2-33) Dimensional Drawing

Safety Notice: Secondary circuits must never be left open when energized. Before maintenance, short-circuit and reliably ground the secondary in accordance with local electrical safety regulations. Do not operate transformer with oil level below minimum marking.

Safety Notes

Ordering Information

When placing an order, the required configuration shall be specified according to the local grid requirements, applicable standards, and project technical specification. The following parameters shall be clearly stated for technical confirmation and production release:

Selection Guidance

  1. Determine rated primary voltage based on system nominal voltage (33 kV or 33/√3 kV).
  2. Select metering and/or protection accuracy requirements (e.g., 0.2 / 0.5 for metering; 6P for protection).
  3. Confirm rated burden (VA) for each secondary circuit based on connected meters/relays and wiring losses.
  4. Verify residual winding requirement for ground fault detection (JDJJ2-35 configuration).
  5. Confirm insulation level matches system insulation coordination requirements.

If local utility or project requirements apply (e.g., altitude correction factors, seismic requirements, special oil specifications, terminal arrangement, mounting constraints, documentation language, or required certificates), specify them at the ordering stage. Special configurations shall be confirmed by technical agreement and final data sheet prior to production.

FAQs

These transformers are used in 35kV AC distribution systems for energy metering, voltage monitoring, and relay protection in outdoor substations and distribution networks. Suitable for urban and rural power distribution applications.

JDJ2-35 features single or dual secondary windings. JDJJ2-35 incorporates a three-winding configuration with residual winding (100/3 V or 100/√3 V) for enhanced ground fault protection capability in systems requiring fault detection.

Oil immersion provides superior insulation properties, enhanced heat dissipation capability, and effective protection against moisture and high-temperature environments, ensuring reliable long-term outdoor service.

Yes. Custom voltage ratios, accuracy class combinations, and secondary outputs can be provided to meet specific application requirements. Contact technical department for customization.

Regular oil level monitoring, periodic oil quality testing per IEC 60296 or equivalent, external insulator cleaning, and grounding system inspection. Maintenance requirements are straightforward for outdoor service.

Grounding terminal, oil level gauge with minimum/maximum markings, oil drain valve, and terminal compartment protection ensure safe operation and maintenance accessibility.

Primary compliance per GB 1208-1997 and IEC 60044-2 (IEC 186). Factory test certificates with traceability to accredited laboratories provided. Oil quality per IEC 60296 or equivalent national standard.

Related Products: