JDZX10-3/6/10A, (REL10) Indoor Epoxy Cast Voltage Transformer

150mm-wide grounded VT with metering and 50VA residual-voltage output for 3–10kV switchgear

  • Phase-to-earth ratios for 3kV, 6kV and 10kV systems provide a 100/√3V measuring output
  • Class 0.2, 0.5, 1 or 3 measurement options deliver 15VA to 200VA by application
  • 3P or 6P auxiliary winding provides 50VA at 100/3V for earth-fault protection
  • Three units can form a Y/Y/open-delta scheme for three-phase voltage and residual monitoring
  • Compact 325 × 150mm base and 290mm mounting length suit REL10-compatible panels

Overview

The JDZX10-3/6/10A/150 (REL10) is an indoor epoxy cast-resin grounded voltage transformer designed for 3kV, 6kV, and 10kV medium-voltage systems, with international voltage classes of 3.6kV, 7.2kV, and 12kV. It features a compact 150mm REL10-style structure and provides secondary outputs of 100/√3V for metering and 100/3V for residual-voltage monitoring.

This transformer supports accurate voltage measurement, energy metering, and relay protection in 50Hz or 60Hz AC systems. It complies with GB20840.3-2013 and IEC61869-3:2011 standards and is suitable for space-constrained indoor switchgear where a grounded VT with dual secondary outputs is required.

JDZX10 k23sa 4 JDZX10 k23sa 6

JDZX10-3/6/10A grounded indoor epoxy voltage transformer for metering and protection

Key Ratings Snapshot

Parameter Rating
System Voltage 3kV / 6kV / 10kV
Voltage Class 3.6kV / 7.2kV / 12kV
Frequency 50Hz / 60Hz
Insulation Type Epoxy cast-resin
Primary Connection Phase-to-neutral (grounded)
Metering Output 100/√3 V
Residual Output 100/3 V
Max. Output 350 VA
Ambient Temperature -25°C to +40°C
Weight 19.7 kg
Standards GB20840.3-2013, IEC61869-3:2011

Model Designation

Model Designation

  • J: Voltage transformer
  • D: Single-phase structure
  • Z: Epoxy cast-resin insulation
  • X: Grounded type with residual-voltage function
  • 10: Design series code
  • 3 / 6 / 10: Rated system voltage (kV)
  • A: Compact configuration
  • 150: REL10-style outline size (mm)

Construction

The JDZX10-3/6/10A/150 is constructed with indoor epoxy cast-resin insulation, providing robust dielectric strength and mechanical stability. The core and windings are fully encapsulated in a solid resin body, ensuring protection against moisture, dust, and partial discharge under normal indoor operating conditions. Primary and secondary terminals are integrated into the molded housing, with clear labeling for phase, neutral, and residual connections. The compact 150mm form factor aligns with REL10 mounting dimensions, facilitating installation in standard medium-voltage switchgear compartments without requiring additional support structures.

Technical Parameters

Service Conditions

  • Ambient temperature: -5°C to +40°C
  • Altitude: up to 1000 m above sea level
  • Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%
  • Installation environment: indoor, non-corrosive, free from explosive or flammable gases and conductive dust

Technical Parameters

The JDZX10-3.6/7.2/12A (REL10) is an indoor epoxy cast-resin voltage transformer designed for 3.6kV, 7.2kV, and 12kV insulation classes. It operates within a temperature range of -5°C to +40°C at altitudes up to 1000 m, complies with relevant IEC standards, and supports rated outputs up to 350VA.

Model Variants

Model Rated
Voltage
Ratio
Accuracy Class /
Rated Output
Max.
Output
(VA)
Rated
Insulation
Level
(kV)
JDZX10-3A/150 3/√3 : 0.1/√3 : 0.1/3 0.2/6P — 15/50VA
0.2/3P — 15/50VA
0.5/6P — 30/50VA
0.5/3P — 30/50VA
1.0/6P — 60/50VA
1.0/3P — 60/50VA
3.0/6P — 200/50VA
3.0/3P — 200/50VA
350 3.6/25/40
JDZX10-6A/150 6/√3 : 0.1/√3 : 0.1/3 0.2/6P — 15/50VA
0.2/3P — 15/50VA
0.5/6P — 30/50VA
0.5/3P — 30/50VA
1.0/6P — 60/50VA
1.0/3P — 60/50VA
3.0/6P — 200/50VA
3.0/3P — 200/50VA
350 7.2/30/60
JDZX10-10A/150 10/√3 : 0.1/√3 : 0.1/3 0.2/6P — 15/50VA
0.2/3P — 15/50VA
0.5/6P — 30/50VA
0.5/3P — 30/50VA
1.0/6P — 60/50VA
1.0/3P — 60/50VA
3.0/6P — 200/50VA
3.0/3P — 200/50VA
350 12/42/75
Selection Note: One transformer is supplied with one selected accuracy class and corresponding rated output combination. The 0.1/√3 kV output is normally used for voltage measurement, metering and monitoring. The 0.1/3 kV output is normally used for residual-voltage or open-delta protection circuits. If required parameters exceed the listed scope, parameters should be confirmed by agreement between manufacturer and purchaser.

Installation & Wiring

Installation Diagram

Installation Diagram

The JDZX10-3,6,10A (REL10) voltage transformer is designed for indoor mounting on a flat, rigid surface using the main mounting length of 290mm. Ensure adequate clearance around the unit for ventilation and access to terminals. The overall base dimensions are 325mm in length and 150mm in width, with an approximate weight of 19.7kg.

Wiring Diagram

Wiring Diagram

The wiring diagram illustrates a grounded VT connection with residual-voltage output. Primary terminals are wired according to phase-to-neutral configuration. Secondary terminals may include labels a, b, c, n, da, and dn depending on the specific wiring arrangement. Residual-voltage terminals (da, dn) must be connected in accordance with the relay protection scheme. Verify terminal polarity, proper grounding, and sufficient cabinet clearance before commissioning.

Always confirm correct terminal markings, grounding integrity, and insulation clearances prior to energizing the system. Incorrect wiring may result in equipment damage or safety hazards.

Selection & FAQs

Selection Guide

  • Match the system voltage: select the 3/√3kV, 6/√3kV or 10/√3kV phase-to-earth primary ratio together with the corresponding 3.6kV, 7.2kV or 12kV insulation class.
  • Choose the measuring duty: available combinations include class 0.2 at 15VA, class 0.5 at 30VA, class 1 at 60VA or class 3 at 200VA, plus a 50VA protection winding.
  • Define the protection winding: specify 3P or 6P according to the relay scheme, and confirm the 100/3V residual-voltage connection for the open-delta circuit.
  • Confirm the voltage factor: the rated voltage factor and permissible duration are not stated; they must be selected for the system neutral arrangement and expected earth-fault clearing time.
  • Verify installation details: confirm the 150mm platform, 290mm mounting length, grouped three-unit terminal diagram, operating temperature and secondary fusing before approval.

Frequently Asked Questions

Q1: What voltage classes does this indoor voltage transformer support?

It supports 3.6kV, 7.2kV, and 12kV insulation classes. The epoxy cast-resin design ensures reliable performance for indoor switchgear. Contact us for specific system voltage matching.

Q2: Can this epoxy cast transformer operate at high altitudes?

Standard models are rated for altitudes up to 1000 meters above sea level. For installations exceeding this limit, derating or custom design is required. Please confirm your site altitude before ordering.

Q3: Which accuracy classes are available for measurement and protection?

The transformer offers 0.2, 0.5, 1.0, and 3.0 classes for measurement, alongside 3P and 6P for protection. Maximum rated output reaches 350VA. Specify your required accuracy and burden during inquiry.

Q4: Does this voltage transformer comply with international IEC standards?

Yes, the JDZX10 series is manufactured in full compliance with relevant IEC standards. This ensures global compatibility for your medium-voltage projects. Request the specific type test report for your records.

Q5: How can we order custom voltage ratios for our project?

Standard ratios like 3/√3 and 6/√3 are readily available. Custom ratios and specific accuracy classes are subject to factory confirmation. Please provide your exact requirements for a formal quotation.

Q6: Where is this epoxy cast voltage transformer typically installed?

It is strictly for indoor installation in non-corrosive environments free from explosive gases. The cast-resin construction prevents conductive dust ingress. Verify your site conditions before deployment.

Q7: What are the ambient temperature and humidity limits for installation?

The ambient temperature must remain between -5°C and +40°C. Relative humidity should not exceed 95% daily or 90% monthly averages. Ensure your installation environment meets these conditions.