JDZXF9, JDZX9-35W outdoor cast-resin voltage transformer (35kV VT/PT)

2026-03-02

Product Overview

Functional Definition

The JDZXF9-35W and JDZX9-35 series outdoor cast-resin voltage transformer, are precision electromagnetic instruments designed for accurate voltage measurement, energy metering, and relay protection applications in 35 kV outdoor AC power systems. These transformers utilize electromagnetic induction principles to provide galvanically isolated secondary voltage signals proportional to primary voltage.

Key Ratings

Item Specification (per order / nameplate)
System voltage class 35 kV class (outdoor distribution and transmission applications)
Rated frequency 50 Hz (60 Hz available upon request)
Rated voltage ratio 35000/√3/100/√3 or 35000/√3/100/√3/100/√3 (multi-winding configurations)
Accuracy classes Metering and/or protection windings as specified (e.g., 0.2 / 0.5, 6P)
Rated burden Per winding as specified (VA)
Burden power factor cosφ = 0.8 (inductive) unless otherwise specified by the project standard
Insulation level 40.5/95/200 kV (Um/LIPL/ACWV)
Pollution grade Grade II (Grade IV available)
Applicable standards IEC 61869-3; GB 20840.3-2013; GB 20840.1-2010; GB 1207-2006
Structural variants JDZX9-35 (single protection winding) / JDZXF9-35 (dual metering, single protection winding)

Product Show

JDZXF9, JDZX9-35W outdoor cast-resin voltage transformer (35kV VT/PT)

Working Principle

Operating on Faraday’s law of electromagnetic induction, the voltage transformer features a laminated magnetic core with primary winding connected to the high-voltage line and secondary windings providing standardized low-voltage signals. The magnetic flux generated by primary voltage induces proportional voltage in the secondary winding, delivering standardized output voltage through connected burden.

System Application Position

Structural Overview

Epoxy resin cast construction with fully-enclosed outdoor design ensures superior insulation performance, UV resistance, moisture resistance, and mechanical strength. The support-type mounting configuration provides stable installation in outdoor substations while maintaining excellent electrical clearance and creepage distances for Grade II and Grade IV pollution environments.

Model Designation

JDZXF9 35W JDZX9 35KV Voltage Transformers Outdoor 35kV Cast Resin Insulated Solutions type

Model Code Explanation

Variant Differences

JDZX9-35 features one metering winding and one protection winding, suitable for standard metering and protection applications. JDZXF9-35 features two separate metering windings plus one protection winding, enabling independent metering circuits for dual-custody or backup measurement systems. Both models are electrically equivalent when specified with identical voltage ratios, accuracy classes, burdens, and insulation levels.

Service Conditions

The JDZXF9-35W / JDZX9-35W series voltage transformers are designed for outdoor operation under normal service conditions in medium-voltage power systems.

Engineering Note: The installation location shall comply with applicable electrical safety regulations and provide stable operating conditions throughout the transformer’s service life. Grade IV creepage design available for coastal, industrial, and high-contamination areas.

Construction

Construction Design

The epoxy resin casting provides stable insulation properties and resistance to moisture, UV degradation, contamination, thermal cycling, and aging for long-term outdoor service in harsh environments.

Windings & Terminal Marking

JDZXF9 JDZX9 35W Outdoor Cast Resin VT PT output input

Terminal markings follow IEC 61869 and GB 1207 polarity conventions. Under normal operating conditions, when terminal A is at positive potential relative to X, terminals a1/a2/ad are simultaneously at positive potential relative to x1/x2/xd respectively. Correct terminal identification shall be observed to ensure metering and protection performance. At least one point of each secondary winding shall be grounded per safety requirements.

Technical Data

This section provides selection-oriented technical data for the JDZXF9-35 / JDZX9-35 series outdoor, cast-resin voltage transformer used in 35 kV class AC systems (50 Hz / 60 Hz). Data shown below is intended for preliminary selection of voltage ratio, accuracy class combinations, and rated burdens.

Definitions: Accuracy class combination indicates available metering/protection windings in one VT (multi-winding configuration applies). Rated output (VA) is specified per secondary winding. Um is the maximum system voltage. LIPL is lightning impulse protective level. ACWV is AC withstand voltage.

Notation: Voltage ratios expressed as phase-to-ground values (35000/√3 = 20207 V line-to-ground for 35 kV system). Acceptance shall be based on nameplate values and the factory test report.

Data Reference

Model Rated Voltage
Ratio (V)
Accuracy
Class
Combination
Rated
Output
(VA)
Maximum
Output
(VA)
Rated
Insulation
Level (kV)
JDZX9-35 35000/√3 / 100/√3 / 100/3 0.2 / 6P 30 / 100 600 40.5 / 95 / 200
0.5 / 6P 50 / 100
JDZXF9-35 35000/√3 / 100/√3 / 100/√3 / 100/3 0.2 / 0.2 / 6P 20 / 20 / 100 2×300 (metering)
600 (protection)
0.2 / 0.5 / 6P 25 / 30 / 100
0.5 / 0.5 / 6P 30 / 30 / 100
Custom combinations As specified

Note: Custom accuracy class and voltage ratio combinations available upon request. Only one voltage ratio shall be used at a time; simultaneous use of multiple taps is not permitted

Standards & Normative References

Standard Title Application
IEC 61869-1 Instrument Transformers – Part 1: General Requirements General requirements
IEC 61869-3 Instrument Transformers – Part 3: Additional Requirements for Voltage Transformers VT-specific requirements
GB 20840.1-2010 Instrument Transformers – Part 1: General Requirements National standard (aligned with IEC 61869 framework)
GB 20840.3-2013 Instrument Transformers – Part 3: Voltage Transformers National VT requirements (aligned with IEC 61869-3)
GB 1207-2006 Electromagnetic Voltage Transformers National VT standard where specified by the project
IEC 60507 Artificial Pollution Tests on High-Voltage Insulators Pollution grade verification
IEC 60085 Electrical Insulation – Thermal Evaluation Insulation thermal class evaluation reference

Factory Testing Compliance

Installation & Dimensions

Outline

JDZXF9 35W JDZX9 35KV Outdoor Cast Resin Insulated Voltage Transformers outline1

Wiring Principles

JDZXF9 35W JDZX9 35KV Outdoor Cast Resin Insulated Voltage Transformers wiring

Safety Notice: Secondary circuits must maintain at least one grounded point per winding for personnel safety. Before maintenance, disconnect and safely ground all primary circuits in accordance with local electrical safety regulations. Always verify de-energization before approaching equipment.

Safety Notes

Ordering Information

When placing an order, the required configuration shall be specified according to the local grid requirements, applicable standards, and project technical specification. The following parameters shall be clearly stated for technical confirmation and production release:

If local utility or project requirements apply (e.g., specific test certificates, terminal arrangement, mounting constraints, documentation language, altitude correction factors, or seismic qualification), specify them at the ordering stage. Special configurations shall be confirmed by technical agreement and final data sheet prior to production.

FAQs

For 35 kV systems, voltage ratio is typically 35000/√3/100/√3 (phase-to-ground measurement) or 35000/100 (phase-to-phase measurement). Ratio selection depends on system grounding and metering requirements per utility specification.

Specify separate secondary windings for metering and protection, each with its own accuracy class and rated burden (VA) per IEC 61869-3 and GB 1207-2006. JDZXF9 variant provides dual independent metering windings for redundant measurement.

Rated burden (VA) shall cover total connected load (meter + relay + SCADA + wiring loss) for 100/√3 V or 100 V secondary voltage and shall be confirmed during engineering design with voltage drop calculation.

Grade II provides standard creepage distance for normal outdoor environments. Grade IV (suffix W) provides extended creepage distance for severe pollution environments including coastal areas, heavy industry zones, and desert regions per IEC 60507.

JDZX9-35 (single metering winding) and JDZXF9-35 (dual metering windings) are not directly interchangeable. JDZXF9 is specified when independent metering circuits are required for dual-custody billing, backup measurement, or separate revenue/operational metering.

At least one point of each secondary winding shall be solidly grounded per IEC 61869-1 for personnel safety. Terminal X (or xa/xd) is typically grounded. Verify grounding complies with local utility practice and electrical code.

Nameplate and factory test report prevail. Compliance verified per IEC 61869 series and GB 20840 series. Unit test certificates are traceable to accredited laboratories. Type test reports available upon request for design verification.

Yes. Both 50 Hz and 60 Hz operation are supported with same electrical ratings. Specify 60 Hz requirement at order stage. No derating required for 60 Hz operation within specified burden range.