Overview
The JN15-12 is an indoor high voltage earthing switch for three-phase 50 Hz power systems rated 12 kV and below. It is designed to work together with high voltage switchgear cubicles of various types as the protective earthing element, and its performance complies with GB 1985-89 (AC high voltage disconnectors and earthing switches) and IEC 129. The design is advanced and technically reliable, the structure is simple for easy installation, commissioning and adjustment, and the switch has a fast opening and closing capability.
Under voltage but without load it bonds the de-energised circuit to earth for maintenance safety, and can close onto a short-circuit current. It is rated 31.5 kA for 4 s short-time withstand current with 80 kA peak and short-circuit making current, and is supplied with phase-center distances of 210, 230, 250 and 275 mm to suit different cubicles.



Model Designation

The type is designated J N 15 – 12 / □ – □ and decoded as follows:
- J — earthing switch
- N — place of use: indoor
- 15 — design sequence number
- 12 — rated voltage in kV
- □ — rated short-time withstand current in kA (e.g. 31.5)
- □ — phase-center (between-pole) distance in mm
Construction and Operation
The JN15-12 carries its three earth knives on support insulators above a common frame, driven through a transmission shaft by a manual operating mechanism so that all three poles make or break the earth connection together with a fast, positive action. The contacts are dimensioned to close reliably onto a short-circuit current, and the mechanism can be interlocked with the associated switchgear or cubicle door to prevent mal-operation. Its compact three-pole assembly mounts inside or on high voltage switchgear cubicles, and the frame is bonded to the earth network to complete the protective path.
Technical Parameters
Rated Parameters
| No. | Item | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | kV | 12 |
| 2 | Rated frequency | Hz | 50 |
| 3 | Rated short-time withstand current | kA | 31.5 |
| 4 | Rated short-circuit duration | s | 4 |
| 5 | Rated peak withstand current | kA | 80 |
| 6 | Rated short-circuit making current | kA | 80 |
| 7 | Phase-center (between-pole) distance | mm | 210 / 230 / 250 / 275 |
| 8 | 1 min power-frequency withstand voltage | kV | 42 / 48 |
| 9 | Lightning impulse withstand voltage | kV | per technical agreement |
| 10 | Standard | — | GB 1985-89; IEC 129 |
Normal Service Conditions
- Altitude: not above 1000 m
- Ambient temperature: upper limit +40℃, lower limit −10℃
- Seismic: intensity not above 8 degrees
- Site: free from fire, explosion hazard, severe dust, chemical corrosion and severe vibration
Installation & Wiring
Installation and Mounting
Fix the earthing-switch frame to the cubicle mounting plane through the C10 × 19 oval holes at the selected phase-center distance, keeping the earth knives and contacts clear of obstructions. Couple the three poles to the manual operating mechanism through the transmission shaft, then verify simultaneous and full contact seating of all three poles, correct interlock action and bonding of the frame to the earth network before energising.

Outline & Mounting Dimensions
| Model | L (mm) | E (mm) | C (mm) |
|---|---|---|---|
| JN15-12/31.5-210 | 655 | 210 | 516 |
| JN15-12/31.5-230 | 710 | 230 | 556 |
| JN15-12/31.5-250 | 760 | 250 | 596 |
| JN15-12/31.5-275 | 810 | 275 | 646 |
E is the phase-center distance; mounting holes C10 × 19 (96 / 240 / 25 detail).
Selection & FAQs
Ordering Information
- When ordering, state the full model, rated voltage, rated short-time withstand current and phase-center distance, together with any accessory requirement.
- Select the phase-center distance (210 / 230 / 250 / 275 mm) to match the cubicle busbar layout.
- Any special requirement is to be settled between the user and the manufacturer.
Frequently Asked Questions
Q1: What does the type designation JN15-12 mean?
J is the earthing switch, N the indoor place of use and 15 the design sequence number; 12 is the rated voltage in kV. The trailing figures give the rated short-time withstand current in kA and the phase-center distance in mm.
Q2: What is the JN15-12 used for?
It is a protective earthing switch used together with high voltage switchgear cubicles of various types in 12 kV and below, 50 Hz systems, to earth the de-energised circuit for maintenance safety.
Q3: What are the rated values?
Rated voltage 12 kV at 50 Hz, rated short-time withstand current 31.5 kA for 4 s, rated peak withstand current 80 kA and rated short-circuit making current 80 kA.
Q4: Which standards does it comply with?
Its performance complies with GB 1985-89 for AC high voltage disconnectors and earthing switches, and with IEC 129.
Q5: What phase-center distances are available?
Four types — 210, 230, 250 and 275 mm (models JN15-12/31.5-210, -230, -250 and -275), with overall length L of 655, 710, 760 and 810 mm respectively.
Q6: Where can I see related products?
See the high voltage earthing switches range for related models.