Overview
The JN4-12(G) is an indoor high voltage earthing switch for three-phase 50 Hz systems rated 12 kV. It is a main component of 12 kV metal-clad withdrawable switchgear and other indoor high voltage equipment, and may also be used separately for grounding protection; the G designation denotes the plateau (high-altitude) version. It has a short-circuit making capacity, with a reasonable compact structure, small size, flexible operation and easy installation and adjustment.
Under voltage but without load it earths the de-energised circuit for maintenance safety, and can close onto short-circuit current. It is rated 20 kA 4 s short-time withstand current with 50 kA peak and short-circuit making current, and is supplied with phase-center distances of 210, 230 and 250 mm to suit different cubicles.



Model Designation

The type is designated J N 4 – 12 G / □ – □ and decoded as follows:
- J — earthing switch
- N — place of use: indoor
- 4 — design sequence number
- 12 — rated voltage in kV
- G — plateau (high-altitude) type
- □ — rated short-time withstand current in kA
- □ — phase-center (between-pole) distance in mm
Construction and Operation
The JN4-12(G) mounts its three earth knives on support insulators over a common frame, driven through a transmission shaft by a manual operating mechanism so that all three poles make or break the earth connection together. The knives and contacts are designed to close reliably onto a short-circuit current, and the mechanism can be interlocked with the associated circuit breaker or the cubicle door to prevent mal-operation. Its compact three-pole assembly fits inside metal-enclosed switchgear or can be installed as a separate earthing section, and the frame is bonded to the earth network to complete the protective path.
Technical Parameters
Rated Parameters
| No. | Item | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | kV | 12 |
| 2 | Rated frequency | Hz | 50 |
| 3 | Rated short-time withstand current | kA | 20 |
| 4 | Rated short-time withstand duration | s | 4 |
| 5 | Rated peak withstand current | kA | 50 |
| 6 | Rated short-circuit making current | kA | 50 |
| 7 | Phase-center (between-pole) distance | mm | 210 / 230 / 250 |
| 8 | 1 min power-frequency withstand voltage | kV | 42 |
| 9 | Lightning impulse withstand voltage | kV | per technical agreement |
Normal Service Conditions
- Altitude: not above 1000 m
- Ambient temperature: upper limit +40℃, lower limit −10℃
- Seismic: intensity not above 8 degrees
- Site: free from fire, explosion hazard, severe dust, chemical corrosion and severe vibration
Installation & Wiring
Installation and Mounting
Fix the earthing-switch frame to the cubicle mounting plane through the 2 × Ø 13 holes at the selected phase-center distance, keeping the earth knives and contacts clear of obstructions. Couple the three poles to the manual operating mechanism through the transmission shaft, then verify simultaneous and full contact seating of all three poles, correct interlock action and bonding of the frame to the earth network before energising.

Outline & Mounting Dimensions
| Model | A (mm) | B (mm) | C (mm) |
|---|---|---|---|
| JN4-12G/20-210 | 752 | 210 | 628 |
| JN4-12G/20-230 | 792 | 230 | 668 |
| JN4-12G/20-250 | 832 | 250 | 708 |
B is the phase-center distance; mounting holes 2 × Ø 13 (30 mm / 60 mm detail).
Selection & FAQs
Ordering Information
- When ordering, state the full model, rated voltage, rated short-time withstand current, phase-center distance and the operating-arm position (left or right), and whether a live-display device is required.
- Select the phase-center distance (210 / 230 / 250 mm) to match the cubicle busbar layout.
- Any special requirement is to be settled between the user and the manufacturer.
Frequently Asked Questions
Q1: What does the type designation JN4-12(G) mean?
J is the earthing switch, N the indoor place of use and 4 the design sequence number; 12 is the rated voltage in kV and G denotes the plateau (high-altitude) version. The trailing figures give the rated short-time withstand current in kA and the phase-center distance in mm.
Q2: What is the JN4-12 used for?
It is a main earthing component of 12 kV metal-clad withdrawable switchgear and other indoor high voltage equipment, used to earth the de-energised circuit for maintenance safety and, where required, used separately.
Q3: What are the rated values?
Rated voltage 12 kV at 50 Hz, rated short-time withstand current 20 kA for 4 s, rated peak withstand current 50 kA and rated short-circuit making current 50 kA.
Q4: Can the earthing switch close onto a fault?
Yes. It has a rated short-circuit making current of 50 kA, so it can close reliably onto a short-circuit current; it is still operated only under voltage but without load for normal switching.
Q5: What phase-center distances are available?
Three types — 210, 230 and 250 mm (models JN4-12G/20-210, -230 and -250), with overall dimensions A of 752, 792 and 832 mm respectively.
Q6: Where can I see related products?
See the high voltage earthing switches range for related models.