FDGE8 Semi-Enclosed Dry Type Discharge Coil

FDGE8 semi-enclosed dry type discharge coil for indoor 50Hz AC systems up to 10kV, discharging HV shunt capacitor banks.

  • Rated voltage 6.6-12kV with discharge capacity from 1.7 to 3.4Mvar
  • Accuracy class 0.2, 0.5, or 1 with rated secondary output up to 100VA
  • Discharges capacitor residual voltage to safe value within 5 seconds
  • Iron-core semi-casting structure built with silicon steel sheets
  • Rated insulation level up to 12/42/75kV with >300mm creepage distance
  • Secondary winding provides voltage indication and optional relay output

The FDGE8 semi-enclosed dry type discharge coil is an epoxy resin vacuum-cast, single-phase indoor product for AC power systems at 50Hz with a rated voltage of 10kV and below. It is connected in parallel with the high-voltage shunt capacitor bank. When the capacitor group is disconnected from the system, the coil reduces the residual voltage of the capacitor bank to a safe value within five seconds. During normal operation the secondary winding functions as a voltage indicator; where users require it, a residual voltage winding can be provided to deliver relay protection.

The coil adopts an iron-core semi-casting structure in which the core is built from high-grade silicon-steel sheets. The result is a compact, light-weight unit with low no-load loss, strong resistance to over-voltage, and convenient installation that requires no maintenance. It is designed as a maintenance-free replacement for conventional oil-immersed discharge coils in capacitor bank compensation installations.

FDGE8 semi-enclosed dry type discharge coil product display, epoxy resin bushings, laminated core and mounting base details
FDGE8 semi-enclosed dry type discharge coil poster, rated voltage 6.6-12kV, fast discharge within 5 seconds, epoxy resin cast

Key Ratings Snapshot

Item Value
System frequency 50Hz
Rated primary voltage 6.6/√3, 7.2/√3, 11/√3, 12/√3 kV
Rated secondary voltage 0.1 kV
Accuracy class / rated output 0.2 → 20VA; 0.5 → 50VA; 1 → 100VA
Discharge capacity 1.7 / 2.5 / 3.4 Mvar
Rated insulation level 7.2/32/60 kV; 12/42/75 kV
Residual discharge time ≤ 5s to safe voltage
Surface creepage distance > 300mm
Load power factor cosφ 0.8 (lagging)
Phase / installation Single phase / indoor
Standard DL/T 653-1998

Operating Function

The discharge coil is connected in parallel across the terminals of the high-voltage shunt capacitor bank. While the bank is energized, the coil operates as a voltage transformer, and its secondary winding supplies a proportional low voltage used for voltage indication. When the capacitor bank is switched off, the stored electrostatic energy of the capacitors discharges through the coil windings; the coil presents a controlled impedance path that drains the residual voltage to a safe level within five seconds, protecting personnel and downstream equipment. If a residual voltage winding is fitted, its output can drive a relay to provide unbalance or residual-voltage protection for the capacitor bank.

Construction and Design

The FDGE8 uses an iron-core semi-casting (semi-enclosed) structure. The magnetic core is stacked from high-grade silicon-steel sheets to keep no-load loss low and to provide strong over-voltage withstand capability. Windings are encapsulated by epoxy resin vacuum casting, giving a moisture-proof, maintenance-free insulation system suited to indoor switchgear and capacitor compartments. The semi-enclosed frame keeps the unit compact and light while allowing convenient mounting; base fixing holes and terminal arrangement suit standard capacitor bank layouts.

Model Designation

  • FD — Discharge coil
  • G — Dry type
  • E — With secondary winding
  • 8 — Design sequence number
  • / □ — Rated primary voltage, kV
  • — Maximum matched capacitor capacity, Mvar
  • – 1 — Single phase

Example: FDGE8/11/√3-2.5-1 denotes a dry-type discharge coil with secondary winding, design No.8, rated primary voltage 11/√3 kV, matched capacitor capacity 2.5Mvar, single phase.

FDGE8 model designation meaning: FD discharge coil, G dry type, E with secondary winding, 8 design number, rated primary voltage kV, max capacitor capacity Mvar, single phase

Technical Parameters

Service Conditions

  • Installation position: Indoor type
  • Ambient temperature: -5℃ ~ +40℃
  • Altitude: Not more than 1000m
  • Atmosphere: No corrosive gas or smoke; no conducting or explosive dust
  • Vibration: No severe mechanical vibration at the installation site
  • Relative humidity: Monthly average ≤ 90%; daily average ≤ 95%

Technical Data

Type Rated

voltage (kV)

Accuracy class

& rated secondary

output (VA)

Discharge

capacity (Mvar)

Rated

insulation

level (kV)

0.2 0.5 1
FDGE8/6.6/√3-1.7-1 6.6/√3/0.1 20 50 100 1.7 7.2/32/60
FDGE8/7.2/√3-1.7-1 7.2/√3/0.1 1.7 7.2/32/60
FDGE8/11/√3-1.7-1 11/√3/0.1 1.7 12/42/75
FDGE8/11/√3-2.5-1 11/√3/0.1 2.5 12/42/75
FDGE8/11/√3-3.4-1 11/√3/0.1 3.4 12/42/75
FDGE8/12/√3-1.7-1 12/√3/0.1 1.7 12/42/75
FDGE8/12/√3-2.5-1 12/√3/0.1 2.5 12/42/75
FDGE8/12/√3-3.4-1 12/√3/0.1 3.4 12/42/75

Standards

  • DL/T 653-1998 《Specification of discharge coils for high voltage parallel connection capacitor for order》
  • Load power factor: cosφ 0.8 (lagging)
  • Surface creepage distance: more than 300mm
Note: rated voltage ratio and secondary voltage (e.g. 100 V) can be customized upon technical agreement. Final parameters are subject to nameplate data and approved specifications.

Installation & Wiring

Installation Diagram

Overall dimensions (mm): top width 180; height 530±5; base mounting 90 / 200±1 (front), 170 / 230±1 (side). Refer to the approved outline drawing before foundation and busbar work.

FDGE8 semi-enclosed dry type discharge coil installation diagram, overall dimensions Figure 1 and Figure 2

Wiring Diagram

The primary winding is connected in parallel across the high-voltage capacitor bank terminals (phase to neutral/earth point of the bank). The secondary winding supplies voltage indication; where fitted, the residual voltage winding connects to the protection relay. Confirm terminal markings, polarity and earthing against the approved wiring drawing before energization.

FDGE8 semi-enclosed dry type discharge coil wiring diagram: primary winding connection, secondary winding connection and voltage relay connection

Applications

  • HV shunt capacitor banks in substations and distribution networks (6.6-12kV)
  • Reactive power compensation and power-factor correction installations
  • Capacitor bank protection schemes requiring residual-voltage relay input
  • Indoor switchgear and capacitor compartments replacing oil-immersed discharge coils
Safety warning: installation and maintenance must be performed by qualified professionals. Verify model, voltage ratio, terminal markings and grounding before energizing. The secondary circuit must include adequate fuse protection and must never be short-circuited during operation.

Selection & FAQs

Selection Guide

  • State the rated primary voltage. Choose from 6.6/√3, 7.2/√3, 11/√3 or 12/√3 kV to match the capacitor bank system voltage.
  • State the capacitor bank capacity (Mvar). Select the matched discharge capacity 1.7, 2.5 or 3.4 Mvar; do not order by model code alone.
  • Confirm system frequency and secondary use. 50Hz; specify whether the secondary is for voltage indication only or whether a residual voltage winding is required for relay protection.
  • Specify accuracy class and burden. 0.2 (20VA), 0.5 (50VA) or 1 (100VA) according to the connected metering/protection load.
  • Confirm insulation level and environment. 7.2/32/60 or 12/42/75 kV; verify indoor installation, altitude ≤1000m and ambient -5℃~+40℃.

FAQs

Q1: What does the discharge coil do when the capacitor bank is switched off?

It provides a controlled discharge path so the capacitor bank residual voltage falls to a safe level within five seconds, protecting personnel and equipment.

Q2: Can the secondary winding be used for voltage indication?

Yes. During normal operation the secondary winding outputs a proportional low voltage suitable for voltage indication.

Q3: Is relay protection available?

On request a residual voltage winding can be provided to supply a relay for residual-voltage / unbalance protection of the capacitor bank.

Q4: Which voltage ratings and capacities are available?

Rated primary 6.6/√3, 7.2/√3, 11/√3 and 12/√3 kV with matched discharge capacities of 1.7, 2.5 and 3.4 Mvar; insulation level 7.2/32/60 or 12/42/75 kV.

Q5: Does it need maintenance?

No. The epoxy resin vacuum-cast, iron-core semi-casting design is maintenance-free, unlike oil-immersed discharge coils that require oil handling and testing.

Q6: What standard does the FDGE8 comply with?

It is manufactured in accordance with DL/T 653-1998, with load power factor cosφ 0.8 (lagging) and surface creepage distance greater than 300mm.