Secondary Burden Impact on Current Transformer Accuracy Classes: Mechanism Analysis and Calibration Strategy

2026-02-28

Secondary Burden Impact on Current Transformer Accuracy Classes: Mechanism Analysis and Calibration Strategy

Problem Definition: Accuracy Class Degradation in Field Applications

In industrial power systems, current transformers (CTs) specified with 0.2S or 0.5 accuracy classes frequently exhibit measurement errors exceeding their rated specifications during actual operation. Field investigations reveal that the primary culprit is not manufacturing defects but rather secondary burden mismatch between design assumptions and real-world installations. When CTs are installed with secondary cable lengths exceeding 100 meters or connected to multiple metering devices simultaneously, the total burden can easily surpass the rated burden, causing accuracy class degradation from 0.2S to worse than 1.0 class.

Standard Requirements: IEC 61869-2 Burden Classification and Testing

IEC 61869-2 standard defines accuracy classes based on specific burden conditions. For 0.2S class CTs, the standard requires error limits of ±0.2% for ratio error and ±10 minutes for phase displacement at 100% rated current, but crucially, these specifications are valid only when operating at the rated burden (typically 10VA, 15VA, or 30VA). The standard mandates burden testing at multiple points: 25%, 100%, and 120% of rated burden to verify performance across the operational range.

The burden itself is defined as Zb = Rwire + Rinstrument + XL, where Rwire is the resistance of secondary cables, Rinstrument is the resistance of connected devices, and XL is the inductive reactance. For accurate classification, the power factor of the burden must also be considered, with standards typically assuming cosφ = 0.8 lagging.

Mechanism Analysis: How Burden Affects Magnetic Circuit Performance

The relationship between secondary burden and CT accuracy is governed by fundamental electromagnetic principles. The CT’s magnetic circuit must satisfy the equation:

Vsec = Isec × Zb = 4.44 × f × Nsec × Bmax × Acore

Where Vsec is secondary voltage, Isec is secondary current, Zb is burden impedance, f is frequency, Nsec is secondary turns, Bmax is maximum flux density, and Acore is core cross-sectional area.

When burden increases beyond design specifications, Vsec must increase proportionally to maintain the same Isec. This forces Bmax higher, potentially driving the core closer to saturation. Near saturation, the magnetizing current Im increases non-linearly, creating additional phase shift and ratio error.

The impact is particularly severe at low current levels (5-20% of rated current), where the signal-to-noise ratio is already compromised. At 5% rated current with excessive burden, a 0.2S class CT can exhibit errors exceeding 2.0%, rendering it useless for revenue metering applications.

Design Trade-offs and Customization: Optimizing for Real-World Burden Conditions

Manufacturers face critical trade-offs when designing CTs for specific burden conditions:

Customization strategies include:

  1. Burden-Specific Design: Specify actual field burden during ordering rather than using standard burden ratings
  2. Dual-Ratio Windings: Provide multiple secondary taps to match different burden conditions
  3. Enhanced Core Materials: Use grain-oriented silicon steel or amorphous metal cores for improved low-burden performance
  4. Compensated Windings: Implement turn compensation to offset burden-induced errors

Engineering Implementation: Burden Calculation and Verification Protocol

Field Burden Calculation Checklist:

  1. Measure secondary cable resistance (Rcable = 2 × ρ × L / A, where ρ = 0.0172 Ω·mm²/m for copper)
  2. Sum instrument burdens from all connected devices (meters, relays, transducers)
  3. Calculate total burden: Ztotal = √[(Rcable + Rinstruments)² + XL²]
  4. Verify Ztotal ≤ CT rated burden at specified power factor

On-Site Verification Procedure:

  1. Perform burden test at 100% and 5% rated current using calibrated test equipment
  2. Measure actual ratio error and phase displacement
  3. Compare results against accuracy class specifications
  4. If errors exceed limits, either reduce burden or replace with higher-rated CT

Troubleshooting Common Burden-Related Issues:

Conclusion: Matching CT Specifications to Actual Field Conditions

Accuracy class specifications are meaningless without proper burden matching. The key to reliable CT performance lies in accurate burden calculation during design phase and verification during commissioning. For critical metering applications, always specify actual field burden conditions rather than relying on standard burden ratings. When burden cannot be reduced, consider custom-designed CTs with enhanced core materials and optimized winding configurations. Remember that a properly specified 0.5 class CT with matched burden will outperform an improperly applied 0.2S class CT every time.


Related Products:
Documents you may also like:
Top