JLSZV1-6 10W/210 Outdoor Cast-Resin Combined Current and Voltage Transformer

3kV–10kV voltage class for medium-voltage outdoor metering applications

  • Epoxy cast-resin insulation ensures durability and environmental resistance
  • Combines CT and PT in one compact 420mm x 485mm housing
  • Accuracy class 0.2S/0.5 for precise revenue metering
  • Complies with IEC 61869-1 and IEC 61869-2 standards
  • Operates reliably up to 4500m altitude in outdoor conditions
  • Supports both Y-type and L-type primary connection configurations

Overview

The JLSZV1-6 10W/210 is a three-phase outdoor epoxy cast-resin combined instrument transformer rated for 3kV, 6kV, and 10kV medium voltage systems. It integrates both current transformer (CT) and voltage transformer (PT) functions in a single compact housing made with epoxy resin insulation, suitable for outdoor installations up to 4500m altitude.

Designed for revenue metering and system monitoring, it meets accuracy class 0.2S requirements and supports both 50Hz and 60Hz networks. Its compact dimensions (420mm x 485mm) make it ideal for space-constrained applications such as retrofit projects, compact switchgear, and distribution substations with limited bay space.

Product Display

JLSZV1 compact combined instrument transformer for urban substations

Product Display

Key Ratings Snapshot

Parameter Rating
Voltage Class 3kV / 6kV / 10kV
System Frequency 50Hz or 60Hz
Accuracy Class 0.2S (metering)
Primary Current Up to 200A
Insulation Level (10kV model) 12/42/75kV
Insulation Level (6kV model) 7.2/32/60kV
Insulation Level (3kV model) 3.6/25/40kV
Altitude Rating Up to 4500m (no derating)
Phase Configuration Three-phase
Installation Type Outdoor
Insulation Material Epoxy cast-resin
Connection Types Y-type (vertical), L-type (horizontal)

Model Designation

  • J: Instrument transformer
  • L: Combined current and voltage transformer
  • S: Three-phase
  • Z: Epoxy cast-resin insulation
  • V: Outdoor use
  • 1: Design series
  • 3/6/10: System voltage rating in kV
  • W: With voltage transformer winding
  • 210: Primary current rating of 200A (standardized code)
  • -Y: Vertical primary terminal orientation
  • -L: Horizontal primary terminal orientation

Construction

The JLSZV1-6 10W/210 features a monolithic epoxy cast-resin construction that encapsulates both the current and voltage transformer cores and windings in a single solid insulating body. This design provides excellent mechanical strength, moisture resistance, and long-term stability under outdoor environmental conditions. The primary terminals are embedded within the resin housing and configured either vertically (Y-type) or horizontally (L-type) to accommodate different busbar layouts. Secondary terminals are housed in a protected terminal box with IP2X protection, ensuring safe and reliable connections for metering circuits. The absence of oil or gas eliminates leakage risks and reduces maintenance requirements, making it suitable for environmentally sensitive or high-altitude installations.

Technical Parameters

Service Conditions

  • Installation position: Indoor or outdoor switchgear, metering cabinets, or distribution substations
  • Connection type: Y-type (vertical) or L-type (horizontal) per project requirements
  • Ambient temperature: -15°C to +55°C
  • Maximum altitude: ≤ 4500m (no derating required)
  • Mounting method: Floor-mounted or panel-mounted depending on configuration
  • Grounding: Connect grounding terminal per local electrical codes

Technical Parameters

The JLSZV1-6/10W/210 is a compact outdoor epoxy cast-resin combined instrument transformer designed for 3kV, 6kV, and 10kV metering applications. It features an operating temperature range of -15°C to +55°C, supports installation up to 4500m altitude without derating, complies with GB20840.4-2015, and offers primary current options from 5A to 200A.

Voltage Transformer Data

Type
(Ratio)
Rated
Insulation
Level
(kV)
Accuracy Class
(Protection/
Measurement)
Burden
(VA)
Rated
Output
(VA)
JLSZV1-3W/210
3000/100
3.6/25/40 0.2 / 0.5 15 / 30 300
JLSZV1-6W/210
6000/100
7.2/32/60 0.2 / 0.5 15 / 30 300
JLSZV1-10W/210
10000/100
12/42/75 0.2 / 0.5 15 / 30 300

Current Transformer Data

Parameter Value
Rated
Primary
Current
(A)
5 – 200 (selectable ratios)
Rated
Secondary
Current
(A)
5
Short-Time
Thermal
Current
80 × In
Dynamic
Current
200 × In
Rated
Insulation
Level
(kV)
12/42/75
Note: Select model variant (JLSZV1-3W/210, JLSZV1-6W/210, or JLSZV1-10W/210) based on system voltage. Primary current ratio must be specified at time of order.

Installation & Wiring

Installation Diagram

Installation Diagram 1
Installation Diagram 2

The JLSZV1-6 10W/210 combined transformer is designed for floor or platform mounting using the base dimensions of 280mm x 355mm. Mounting hole spacing must follow the provided installation drawing. Two configurations are available: Y-type (vertical primary connection) and L-type (horizontal primary connection), selected based on system layout and cable entry requirements.

Wiring Diagram

Wiring Diagram

Primary terminals are labeled AP1, AP2 (Phase A) and CP1, CP2 (Phase C). For Y-type units, these are arranged vertically; for L-type, horizontally. Secondary connections are made inside the sealed terminal box, which supports separate metering and protection circuits as required by the application. The grounding terminal uses an M8 bolt for frame grounding in compliance with local electrical codes.

Always de-energize and verify isolation before making any electrical connections. Follow local regulations and manufacturer instructions to ensure safe and compliant installation.

Selection & FAQs

Selection Guide

  • Select the correct voltage rating: 3W for 3kV, 6W for 6kV, or 10W for 10kV systems.
  • Choose between Y-type (vertical) or L-type (horizontal) primary connections based on your switchgear busbar layout.
  • Specify the CT primary current rating (e.g., 50A, 100A, 200A) according to expected load conditions.
  • For revenue metering, select CT accuracy class 0.2S and PT accuracy class 0.2; for monitoring, use CT 0.2 and PT 0.5.
  • Ensure installation space accommodates the compact dimensions (420mm x 485mm) and weight (85kg), and confirm altitude does not exceed 4500m.

Frequently Asked Questions

Q1: How should this combined transformer be mounted outdoors?

It supports floor-mounted or panel-mounted configurations in outdoor switchgear. Ensure the grounding terminal is connected per local electrical codes. Contact us for specific mounting drawings.

Q2: Which accuracy class is available for the voltage transformer?

The unit offers 0.2 class for measurement and 0.5 class for protection. Rated output is 300 VA with 15 or 30 VA burden. Confirm your exact burden requirements with our engineering team.

Q3: Can this 10kV epoxy cast-resin transformer operate at high altitudes?

Yes, it operates up to 4500m maximum altitude without requiring any derating. The ambient temperature range is -15°C to +55°C. Specify your exact site altitude during the inquiry.

Q4: What compliance standards does this instrument transformer meet?

The JLSZV1-6 series complies with the GB20840.4-2015 standard. It is designed for 3kV, 6kV, and 10kV metering applications. Request the full type test report for your project compliance.

Q5: What primary current options are available for this model?

Primary current options range from 5A to 200A depending on your metering needs. The connection type can be configured as Y-type (vertical) or L-type (horizontal). Contact sales for custom ratio availability.

Q6: Where is this combined current and voltage transformer applied?

It is primarily used in outdoor switchgear, metering cabinets, and distribution substations. This compact epoxy cast-resin design integrates both CT and VT functions. Check our catalog for similar medium-voltage instrument transformers.

Inquiry for JLSZV1-6 10W/210 Outdoor Cast-Resin Combined Current and Voltage Transformer: